TL;DR —B2B Compliance Quick Read
-
The F-Gas Regulation (EU) 517/2014 continues to drive the HFC phase-down through 2026 and beyond —the 2026 step takes the EU-wide HFC quota down to ~17% of the 2015 baseline.
-
Five B2B compliance items drive operational risk: refrigerant type, quota allocation, leak-check obligations, recovery certification, and record-keeping.
-
The compliance items apply differently to refrigerant producers, importers, distributors, refrigeration installers, and end-user equipment operators.
-
Low-GWP refrigerant substitution —R-454B, R-32, R-1234yf, R-1234ze(E) —is the operational answer for new equipment, with retrofit accounting for the existing equipment market.
The EU F-Gas Regulation is the regulatory framework that determines which refrigerants can be sold, imported, distributed, and serviced in the European market. The phase-down schedule —a stepped reduction of the EU-wide HFC quota, expressed as a percentage of the 2015 baseline —has been compressing the available quota annually since 2018, and the 2026 step continues the compression. For B2B companies operating in or selling into the EU refrigeration market, the 2026 phase-down step is the trigger for five specific compliance items that determine whether the operation is legal, audit-ready, and prepared for the next compression step.
Xinchang Weien Import & Export Co., Ltd. (Compressorweien) operates in the refrigeration components and refrigerant lubricants space —the company's Refrigerants & Lubricants category and the broader refrigeration compressor and spare-parts catalogue serve EU, North American, and Asian markets. The about page documents the export-channel operating context, and the contact page is the route for buyers who need refrigerant-source or compressor-source support for EU-market refrigeration programs.
This guide is written for the B2B refrigeration buyer, distributor, importer, service-company operator, and equipment OEM who needs a working understanding of the F-Gas phase-down and its operational implications. It covers the regulatory framework, the five compliance items that determine operational legality, the low-GWP refrigerant options that address the phase-down, and the operational workflow that brings a B2B operation into compliance. If you take only one thing from this article, take this: the F-Gas phase-down is not a five-year push —it is a permanent operational constraint, and the compliance items apply cumulatively across the operation's product, service, and record-keeping workflows.

The F-Gas Regulatory Framework: EU 517/2014 and the 2024 Revision
The EU F-Gas Regulation (EU) 517/2014 is the controlling regulation for fluorinated greenhouse gases (F-gases) in the European Union. The regulation establishes a phase-down schedule for hydrofluorocarbons (HFCs) —the most common refrigerant family —expressed as a percentage of the EU-wide HFC quota baseline established in 2015. Each year, the available quota is reduced by a percentage step, and the compressed quota pushes the refrigerant-supplier ecosystem toward lower-GWP alternatives.
The phase-down schedule through 2026:
-
2015: 100% baseline quota
-
2018: 93% of baseline
-
2021: 45% of baseline (the major compression step)
-
2024: 31% of baseline
-
2026: ~17% of baseline (the current step)
-
2027 onwards: further compression steps continuing toward the 2030 target
In 2024, the EU adopted a revised F-Gas Regulation (EU) 2024/573 that accelerates the phase-down and adds new substance restrictions. The revised regulation tightens the available HFC quota further and accelerates the transition to low-GWP refrigerants in key application categories. For B2B refrigeration companies selling into the EU, both the 517/2014 framework and the 2024/573 revisions are the operational reality.
The practical effect of the phase-down is that the supply of high-GWP HFC refrigerants (R-404A, R-507, R-422D in their high-GWP forms, R-23 in stationary applications) is being compressed annually, while the supply of low-GWP alternatives (R-454B, R-32, R-1234yf, R-1234ze(E), HFOs and HFC/HFO blends) is expanding. A B2B operation that is still specifying high-GWP HFCs for new EU equipment in 2026 is buying a refrigerant that is becoming structurally more expensive and harder to source.
The 2026 step is the most operationally consequential year of the phase-down so far. The 2024 step took the quota to 31%; the 2026 step takes it to ~17% —a near-halving of the 2024 quota in two years. The supply-side market response is a sharp price increase on the remaining high-GWP HFCs and a faster migration to low-GWP alternatives. B2B companies that have not migrated their new-equipment specifications to low-GWP refrigerants by 2026 face a compressed-quota bill of materials that is materially more expensive than the bill of materials for a low-GWP-equipped competitor.
The phase-down schedule applies to the EU-wide quota allocated by the European Commission. Quota allocation is by the European Commission (with oversight from the European Environment Agency), and the allocation is granted to HFC producers and importers who hold a quota allocation. Distributors and end users do not hold quota directly; they purchase quota-bearing refrigerant from quota-holding producers and importers. The B2B operational implication is that the distributor and end-user compliance path is to verify that the refrigerant they purchase comes from a quota-holding source —a documentation trail that is documented in the F-Gas register.
Compliance Item 1: Refrigerant Type and GWP Limit
The first compliance item is the refrigerant type itself. The F-Gas Regulation prohibits the use of high-GWP refrigerants in specific application categories and phases in low-GWP alternatives. For B2B refrigeration, the application categories that matter most are stationary refrigeration (commercial and industrial), transport refrigeration (truck and trailer units), and chillers (air-conditioning chillers and process chillers).
The refrigerant-type compliance is refrigerant-specific. R-404A (a high-GWP HFC blend historically dominant in commercial refrigeration) has been restricted in new stationary refrigeration equipment since the early 2020s and is now effectively a legacy refrigerant for the service market only. R-134a (a medium-GWP HFC) is in restricted use across multiple application categories. R-1234yf (a low-GWP HFO) is the dominant low-GWP replacement for medium-temperature commercial refrigeration. R-454B (a low-GWP HFC/HFO blend) is the dominant low-GWP replacement for low- and medium-temperature commercial refrigeration. R-32 (a low-GWP single-component HFC) is the dominant low-GWP replacement for residential and light-commercial air-conditioning.
The refrigerant-type decision is a procurement-decision, not a regulatory-compliance-decision. The F-Gas Regulation's GWP limit constrains the refrigerant-type options; the buyer's procurement decision determines which of the allowed options best fits the equipment's operating profile. A buyer who specifies R-1234yf for a medium-temperature commercial refrigeration system with no documented use-case justification has over-prescribed the refrigerant (R-1234yf is more expensive and has marginally different thermodynamic properties than R-454B for the same application).
The 2024 revision of the F-Gas Regulation added new substance restrictions that affect the medium-term refrigerant supply. The revision restricts additional HFCs and HFC/HFO blends in specific application categories and adds reporting requirements for low-GWP refrigerants that contain specific components. For B2B buyers, the operational implication is that the refrigerant specification in new equipment has to be reviewed against the 2024/573 substance restriction list —a refrigerant that was acceptable in 2023 may not be acceptable in 2026.
Compliance Item 2: Quota Allocation and Verification
The second compliance item is the refrigerant quota. The F-Gas Regulation's phase-down is implemented through an annually-decreasing quota of CO—?equivalent HFCs that can be placed on the EU market by the quota-holding producers and importers. The quota is allocated by the European Commission and reported through the F-Gas quota register.
For B2B refrigerant distributors and end users, the quota compliance path is indirect —they do not hold quota directly, but they purchase quota-bearing refrigerant from quota-holding sources. The compliance item that applies to distributors and end users is the verification that the refrigerant they purchase comes from a quota-holding source. A distributor or end user who purchases refrigerant from a non-quota-holding source is purchasing illegally-placed refrigerant and inherits the regulatory exposure.
The documentation trail for quota compliance includes the supplier's quota allocation documentation (which can be verified through the F-Gas register), the purchase invoice (which should reference the supplier's quota allocation), and the refrigerant label (which should carry the supplier's quota identifier). A distributor or end user who has this documentation trail has the evidence that the refrigerant they hold is legal in the EU market.
The quota documentation is the buyer's defense against illegal-refrigerant exposure. The illegal-refrigerant trade in the EU is a real problem —refrigerant smuggled or illegally placed on the EU market is sold at a discount that reflects the absence of the quota cost, and the buyer who purchases this refrigerant inherits the regulatory exposure if the illegal placement is discovered. The buyer who has the quota documentation trail for every kilogram of refrigerant purchased has the defense against the regulatory follow-up.
For refrigerant producers and importers, the quota compliance is direct —the producer must hold a quota allocation that covers the CO—?equivalent quantity of HFCs placed on the EU market. The quota allocation is requested annually from the European Commission, and the allocation is granted based on historical market share and on a published set of allocation criteria. Producers and importers who are entering the EU market for the first time must purchase quota on the secondary market from existing quota holders, which is a meaningful additional expense for new market entrants.
The operational implication for B2B companies that import refrigerant-containing equipment into the EU (refrigeration units, air-conditioning units, heat pumps) is that the refrigerant pre-charged at the factory is subject to the F-Gas quota. The factory that pre-charges the equipment has to source the refrigerant from a quota-holding supplier, and the buyer who imports the pre-charged equipment is purchasing quota-bearing refrigerant whether the equipment was pre-charged at the factory or charged on-site at the destination.
Compliance Item 3: Leak-Check Obligations
The third compliance item is the leak-check obligation. The F-Gas Regulation requires operators of stationary refrigeration, air-conditioning, and heat-pump equipment above specific charge-size thresholds to perform regular leak checks by certified personnel, and to maintain records of the leak checks for inspection by the relevant national authority.
The leak-check thresholds and frequencies depend on the refrigerant's CO—?equivalent charge size:
-
3 kg or more of F-gases —leak check every 12 months minimum
-
30 kg or more of F-gases —leak check every 6 months minimum
-
300 kg or more of F-gases —leak check every 3 months minimum
-
Leak-detection system installed —leak check every 24 months minimum
The CO—equivalent calculation is the refrigerant mass (in kg) multiplied by the refrigerant's GWP value. For high-GWP refrigerants, the CO—equivalent threshold is reached at relatively low mass-charge levels. For R-404A (GWP ~3,922), the 30 kg CO—equivalent threshold is reached at approximately 7.6 kg of refrigerant charge. For R-454B (GWP ~466), the same threshold is reached at approximately 64 kg of refrigerant charge.
The CO—equivalent calculation determines the leak-check frequency, not the refrigerant mass. An operator who installs a 50 kg R-404A charge has a CO—?equivalent charge of 196,100 kg —well above the 300 kg threshold and therefore requires quarterly leak checks. The same operator who installs a 50 kg R-454B charge has a CO—equivalent charge of 23,300 kg —below the 300 kg threshold and therefore requires only semi-annual leak checks. The leak-check operational burden scales with the CO—equivalent, not the refrigerant mass.
The leak-check obligation also requires leak-detection system installation above the 300 kg CO—equivalent threshold. A leak-detection system is a calibrated sensor system that continuously monitors the refrigerant charge for leaks and triggers an alarm when the leak rate exceeds a defined threshold. The leak-detection system must be checked annually for correct operation. The operational cost of leak-detection system installation is significant for large commercial or industrial refrigeration installations, which is one of the operational drivers toward low-GWP refrigerants in new equipment.
The leak-check record-keeping requirement is the practical operational burden. The operator must maintain a leak-check log that records the date of each check, the certified-leak-check personnel who performed it, the leak rate measured, any repairs performed, and any refrigerant added to replace leaked refrigerant. The leak-check log is the documentation that the relevant national authority reviews at inspection, and a missing or incomplete log is one of the most common F-Gas compliance findings.
Compliance Item 4: Recovery Certification and Personnel Qualification
The fourth compliance item is the refrigerant-recovery certification. The F-Gas Regulation requires that refrigerant be recovered (not vented to atmosphere) at the end of equipment life, at equipment servicing, and at decommissioning. The refrigerant recovery must be performed by certified personnel using certified recovery equipment, and the recovered refrigerant must be either destroyed (through approved destruction technology), reclaimed (purified to refrigerant-grade quality for re-use), or sent for destruction.
The personnel qualification is the certification-and-licensing component. The F-Gas Regulation requires that personnel handling refrigerant recovery, leak checking, and refrigerant charging hold a personal certification issued by a certification body accredited under the regulation. The certification has different levels (category I, II, III, IV depending on the refrigerant mass and the type of work) and the certification must be renewed on the certification body's published schedule (commonly every 5 years).
The recovery equipment certification is the equipment side. Recovery equipment used in the EU must be certified under the regulation and must meet the recovery efficiency standards published in the implementing legislation. The recovery efficiency standard specifies the maximum percentage of refrigerant that can be left in the equipment after recovery —for most refrigerants, the standard is 95%+ recovery efficiency.
Recovery-certification documentation required at equipment decommissioning
- The certified-personnel operator's certification reference
- The recovery equipment's certification reference
- The mass of refrigerant recovered (in kg)
- The refrigerant type recovered
- The destination of the recovered refrigerant (destruction facility, reclaim facility, or transfer documentation)
- The date and location of the recovery
This documentation is what the relevant national authority reviews at equipment decommissioning, and missing documentation is one of the most common F-Gas compliance findings.
The recovery-certification requirement also creates an operational dependency on the certified-refrigerant-reclaim supply chain. Reclaimed refrigerant can be sold for re-use in the EU market, with the documentation trail that verifies the reclamation. The reclaim-supply chain is structurally smaller than the virgin-refrigerant-supply chain, which means reclaim refrigerant is typically more expensive per kilogram than virgin refrigerant, and the reclaim supply is concentrated in specific reclaim operators.
For B2B refrigeration service companies and equipment operators, the recovery-certification requirement means that refrigerant cannot be vented during servicing —the refrigerant must be recovered, documented, and either reclaimed or destroyed. A service company that vents refrigerant during a routine service is in violation of the F-Gas Regulation and inherits the regulatory exposure.
Compliance Item 5: Record-Keeping and the F-Gas Register
The fifth compliance item is the record-keeping obligation and the F-Gas register. The F-Gas Regulation requires operators of equipment above specific charge-size thresholds to maintain a record of the refrigerant charge, the refrigerant additions (replacement refrigerant added during servicing), the refrigerant recoveries (refrigerant removed during servicing or decommissioning), and the leak-check history. The record must be available for inspection by the relevant national authority.
The record-keeping format is not standardized across the EU —the F-Gas Regulation specifies the content of the record, but the format is determined by each member state's implementing legislation. The record can be maintained on paper or electronically, and the typical retention period is 5 years from the date of the last entry.
The F-Gas register is the EU-wide central record of refrigerant quota allocations, quota transfers, and refrigerant equipment registrations. The register is maintained by the European Commission and the European Environment Agency, and the register's data is the audit trail that supports the F-Gas Regulation's enforcement. A B2B company that is audited for F-Gas compliance has its documentation verified against the F-Gas register entries that correspond to its refrigerant purchases and equipment operations.
The F-Gas register is the documentation system's backbone. The quota documentation, the equipment registration, the leak-check records, the recovery records, and the personnel certification records all feed into the F-Gas register. A B2B company that maintains its own records consistent with the F-Gas register has the documentation that survives a regulatory audit; a B2B company that maintains records outside the F-Gas register has the documentation that requires additional verification work at audit.
The record-keeping obligation also applies to refrigerant importers and producers. Importers and producers must report their quota allocations, their quota usage, and the sales of quota-bearing refrigerant. The reporting is quarterly (in most member states) and the reporting must be accurate. Inaccurate reporting is a compliance violation, and systematic inaccurate reporting is a criminal violation in some member states.
For B2B companies that are equipment operators (the operator of a refrigeration or air-conditioning system above the charge threshold), the record-keeping obligation is the operational deliverable that supports the other four compliance items. The leak-check logs, the refrigerant additions and recoveries, the personnel certifications, the recovery documentation, and the equipment registration are all records that the operator maintains and presents at inspection. A B2B operation that has all five compliance items addressed in the record-keeping system has the operational foundation for F-Gas compliance.
Low-GWP Refrigerant Substitution: The Operational Answer
The five compliance items above are the regulatory constraints. The operational answer for new equipment is low-GWP refrigerant substitution —specifying a refrigerant that the F-Gas Regulation allows for the application category and that delivers the required thermodynamic performance. The substitution decision is equipment-specific and operating-profile-specific, and the right refrigerant for one application may be wrong for another.
| Refrigerant |
Type |
GWP (100-yr) |
Typical application |
Notes |
| R-1234yf |
HFO |
< 1 |
Medium-temperature commercial refrigeration, automotive AC |
Lowest GWP among low-flammable alternatives; mild-flammable (ASHRAE A2L classification) |
| R-1234ze(E) |
HFO |
< 1 |
Medium-temperature commercial refrigeration, chillers |
Low GWP; mild-flammable (A2L) |
| R-454B |
HFC/HFO blend |
~466 |
Low- and medium-temperature commercial refrigeration |
Direct R-404A replacement; mild-flammable (A2L); the dominant low-GWP commercial refrigeration refrigerant |
| R-454C |
HFC/HFO blend |
~148 |
Low- and medium-temperature commercial refrigeration |
Lower GWP than R-454B; mild-flammable (A2L) |
| R-32 |
HFC |
~675 |
Residential and light-commercial air-conditioning, heat pumps |
Single-component low-GWP replacement for R-410A; mild-flammable (A2L) |
| CO—?(R-744) |
Natural |
1 |
Commercial refrigeration (trans-critical CO—?systems), heat-pump water heaters |
Non-flammable (A1); requires higher operating pressure; trans-critical cycle requires specific equipment design |
| R-290 (propane) |
Natural |
~3 |
Small commercial refrigeration, domestic refrigerators |
Low GWP; highly flammable (A3); charge-size limits apply |
The substitution decision is driven by the equipment's operating profile (the temperature range, the cooling capacity, the charge size) and by the destination member state's specific F-Gas implementing legislation. The substitution also requires the equipment's component compatibility to be verified —the compressor lubricant (mineral oil vs. POE oil vs. PVE oil) and the elastomer compatibility must be matched to the new refrigerant. A substitution that ignores the lubricant compatibility is a substitution that damages the compressor.
The substitution is more than a refrigerant swap. A new refrigerant may require different lubricants (POE oil instead of mineral oil for HFC refrigerants), different elastomer seals (HFO refrigerants have different elastomer compatibility profiles than HFCs), different pressure settings (HFO refrigerants typically have different discharge pressure profiles than HFCs), and different leak-check protocols (HFO refrigerants are mildly flammable and require additional ventilation in the leak-check procedure). The substitution is an equipment-design change, not a refrigerant change.
For B2B buyers operating in or selling into the EU market, the substitution decision is a procurement-strategic decision rather than a one-time refrigerant change. The substitution roadmap for a B2B operation typically takes 3— years to complete across the equipment fleet, with the substitution prioritized on the equipment categories where the high-GWP refrigerant is approaching the quota-driven price escalation. A B2B operation that begins the substitution roadmap in 2026 will have a meaningful fraction of its fleet on low-GWP refrigerants by 2030, before the next phase-down compression step.
The Compressorweien Refrigerants & Lubricants category provides the refrigerant-source lubricant options that support low-GWP substitution programs. The lubricant selection for a low-GWP refrigerant substitution is one of the operational details that determines whether the substitution is successful in service.
Implementation Workflow: Bringing a B2B Operation into Compliance
The implementation workflow that brings a B2B refrigeration operation into F-Gas compliance has six steps, sequenced over 3—2 months depending on the size of the operation. The workflow addresses all five compliance items and produces the operational documentation that supports ongoing regulatory audit.
-
Step 1 —Refrigerant inventory audit (month 1). Quantify the refrigerant inventory by type, by mass, and by equipment location. The audit establishes the baseline against which the substitution roadmap is measured.
-
Step 2 —Equipment registration audit (months 1—). Document the equipment fleet by type, by refrigerant charge, by CO—?equivalent charge, and by location. The registration audit produces the documentation that supports the leak-check obligation and the F-Gas register entry.
-
Step 3 —Personnel certification audit (months 2—). Document the personnel certifications held by the operation's technicians and service personnel. The audit identifies the gaps that require new certification training.
-
Step 4 —Refrigerant-substitution roadmap (months 3—). Develop the substitution roadmap that migrates the equipment fleet to low-GWP refrigerants over a 3— year horizon. The roadmap prioritizes the highest-impact substitution first (the equipment with the largest high-GWP refrigerant charge).
-
Step 5 —Documentation system implementation (months 4—). Implement the documentation system that supports all five compliance items —the refrigerant inventory, the equipment registration, the leak-check log, the recovery record, the personnel certification record, and the F-Gas register entry.
-
Step 6 —Ongoing operational review (months 6+). Review the documentation quarterly and the substitution roadmap annually. The review is what keeps the compliance posture current against the annually changing regulatory framework.
Compliance-deliverable summary by stakeholder
-
Refrigerant producer / importer: quota allocation, F-Gas register entries, sales documentation
-
Distributor: quota-source verification, sales documentation, customer certification
-
Equipment OEM: refrigerant-type compliance (the 2024/573 substance restrictions), pre-charged equipment documentation
-
Equipment operator: equipment registration, leak-check logs, recovery documentation, personnel certification record, F-Gas register entry
-
Service company: certified-personnel employment, recovery equipment certification, recovery documentation
Frequently Asked Questions
What is the EU F-Gas Regulation in 2026?
The F-Gas Regulation (EU) 517/2014, as revised in 2024 by Regulation (EU) 2024/573, controls fluorinated greenhouse gases in the EU. The 2026 step of the phase-down takes the EU-wide HFC quota to approximately 17% of the 2015 baseline. New substance restrictions under the 2024 revision further restrict specific HFCs and HFC/HFO blends in specific application categories. For B2B refrigeration companies, the operational reality is a continuing compression of the high-GWP HFC supply and a continuing migration toward low-GWP alternatives.
How does the CO—?equivalent calculation affect the leak-check frequency?
The leak-check frequency is set by the refrigerant's CO—?equivalent charge size —the refrigerant mass in kg multiplied by the refrigerant's GWP. The thresholds are 3 kg CO—?equivalent (annual leak check), 30 kg CO—?equivalent (semi-annual), 300 kg CO—?equivalent (quarterly plus leak detection). For R-404A (GWP ~3,922), the 30 kg threshold is reached at approximately 7.6 kg of charge. For R-454B (GWP ~466), the same threshold is reached at approximately 64 kg of charge. The leak-check operational burden scales with the CO—?equivalent, not the refrigerant mass.
What low-GWP refrigerant should I specify for a medium-temperature commercial refrigeration system in 2026?
For medium-temperature commercial refrigeration (supermarket cases, walk-ins, cold storage above 0C), R-454B is the dominant low-GWP refrigerant in the EU market in 2026. R-1234yf is the lowest-GWP option but is less widely available with this implementation and has marginally different thermodynamic properties. For low-temperature commercial refrigeration (below 0C), R-454C is the lowest-GWP option that matches the R-404A performance envelope. For residential and light-commercial air-conditioning, R-32 is the dominant low-GWP replacement for R-410A. The refrigerant specification should be reviewed against the equipment's compressor lubricant, elastomer seals, and pressure settings.
Do I need to upgrade my leak-detection system when I migrate to low-GWP refrigerants?
Potentially. HFO-containing low-GWP refrigerants (R-1234yf, R-1234ze(E), R-454B, R-454C) are mildly flammable (ASHRAE A2L classification), which has implications for the leak-detection system. The refrigerant sensor in the leak-detection system must be calibrated for the new refrigerant —most modern leak-detection systems are multi-refrigerant capable, but the calibration must be updated. The leak-detection system also requires additional ventilation in the equipment room for A2L refrigerants, per the equipment standard and the destination member state's building code. The leak-detection system upgrade is a project that runs in parallel with the refrigerant substitution.
What are the F-Gas penalty provisions?
The F-Gas Regulation is enforced by each member state's national authority, and the penalty provisions vary by member state. Typical penalties include administrative fines (often expressed as a percentage of the operator's annual turnover or as a per-Kilogram CO—?equivalent fine), criminal penalties for systematic non-compliance, and equipment-seizure provisions for illegally-placed refrigerant. The penalty exposure is materially larger than the cost of compliance —a B2B operation that is found in significant non-compliance is exposed to administrative fines that are multiples of the refrigerant purchase cost, plus reputational damage with downstream customers.
How does the 2024/573 revision affect existing refrigerant allocations?
The 2024/573 revision tightens the phase-down schedule, adds new substance restrictions, and adds new reporting requirements. Existing quota allocations are honored under the revised regulation, but the future annual quota reductions are larger than under the 517/2014 schedule. A B2B operation that has a multi-year refrigeration supply contract should verify that the contract's quota-source documentation is consistent with the 2024/573 requirements, particularly for any high-GWP HFCs that are now restricted in specific application categories.
What is the role of reclaimed refrigerant in the EU F-Gas compliance framework?
Reclaimed refrigerant —refrigerant that has been recovered, purified, and tested to refrigerant-grade quality —can be placed on the EU market under the F-Gas Regulation, but the reclaim must be performed by a certified reclamation facility and the reclaimed refrigerant must be documented as reclaimed (not as virgin). The reclaimed refrigerant's quota treatment depends on whether the original virgin refrigerant was quota-bearing; in most member states, reclaimed quota-bearing refrigerant does not require an additional quota allocation for placement on the market. The reclaimed-refrigerant supply is concentrated in specific reclamation operators and is typically more expensive per kilogram than virgin refrigerant.
Can I import pre-charged refrigeration equipment from a non-EU supplier under the F-Gas Regulation?
Yes, but the pre-charged refrigerant counts against the EU's HFC quota, and the importer is responsible for verifying that the refrigerant is quota-bearing. The pre-charged equipment documentation should include the refrigerant type, the refrigerant mass, the supplier's quota documentation, and the equipment's compliance with the relevant equipment standards. A B2B importer that imports pre-charged equipment without the quota documentation inherits the regulatory exposure for the entire pre-charged refrigerant quantity.